GATE EE 2026 — Question 31

Electrical MachinesSingle phase transformer: equivalent circuit, phasor diagram, open circuit and short circuit tests, regulation and efficiencyMSQ1 markMedium

A 220V/12V single-phase transformer is designed for use in India and rated 100 VA at 50 Hz. Later, this unit is shipped to the USA where it is used as a 110V/6V transformer at 60 Hz. Which of the following statements is/are correct?
  1. A
    No-load current drawn would be smaller for operation in the USA compared to that in India
  2. B
    For the same load current, the losses would be higher in the USA compared to that in India
  3. C
    The peak magnetic flux density in the core would be higher while operating in the USA compared to that in India
  4. D
    The eddy current losses in the core would be approximately 44% higher while operating in the USA compared to that in India