A 220V/12V single-phase transformer is designed for use in India and rated 100 VA at 50 Hz. Later, this unit is shipped to the USA where it is used as a 110V/6V transformer at 60 Hz. Which of the following statements is/are correct?
- ANo-load current drawn would be smaller for operation in the USA compared to that in India
- BFor the same load current, the losses would be higher in the USA compared to that in India
- CThe peak magnetic flux density in the core would be higher while operating in the USA compared to that in India
- DThe eddy current losses in the core would be approximately 44% higher while operating in the USA compared to that in India