A system with two generators G1 and G2 (without generator limits) is shown.
The total load on the system is 1184 MW. The expressions for the cost of generation ( and ) and real power loss () are as follows:
Rs/MWh
Rs/MWh
MW
When the generators are operating at their optimal generation, meeting the total load requirement, the real power loss in the system is ________ MW (Round off to one decimal place)
Consider the Lagrange multiplier for optimal generation.